To update to the latest version 2.7.0.7, the HT3xx terminal must have version 2.7.0.6 or higher installed. The reason is described below in the section “Upgrading HT3xx from lower versions to version 2.7.0.7 and higher”.
When upgrading from lower versions (2.6.0.4, 2.7.0.4 and 2.7.0.5), it is first necessary to update the web application to version 2.0.9. This will ensure the upgrade to Domat Visual 2.7.0.6.
The new version 2.7.0.7 and higher includes, in addition to the application and web interface itself, also an operating system update. This change is not only technical – it stems from the requirements of the European Cyber Resilience Act (CRA), which obliges manufacturers to regularly provide security updates, including the operating system. Older versions of the web application cannot handle this process, and the update would fail.
Once you upgrade to version 2.7.0.6, further updates to the latest versions should proceed without issues, in full compliance with the new security standards.
It is possible to upload a new version of the HT3xx application using a web browser by accessing the device’s IP address (the computer with the browser must be in the same network). To access the service web interface, enter the password. In the section Device Management → New application and web on device, select the file “HT300.tar.gz”. The HT3xx will restart automatically.
Do not turn off the power during firmware update!
This version is final for HT200 and no further development will take place. The successor to HT200 is now the HT300 terminal, or larger terminals HT310 and HT315.
It is possible to upload a new version of the HT200 application using a web browser by accessing the device’s IP address (the computer with the browser must be in the same network). To access the service web, enter the password. In the section Device management → New application and web on device, select the file “HT200.sh” (the file name must not be changed). The HT200 will restart automatically.
Do not turn off the power during firmware update!
It is possible to upload a new version of the HT200 application via a web browser using the device’s IP address (the PC with the browser must be on the same network). To access the service web, enter the password. In the section Device management → New application and web on device, select the file “web_2.0.1_Upgrade.tar.gz”.
After this update, the HT200 must be restarted, and the browser must also be closed and reopened. The updated web can be found at the IP address of the HT200. This web interface can be used only to upload the file “HT200_full.sh”. The device will restart automatically after this update. The web page should refresh automatically.
The mobile version of Domat Visual is available for free on Google Play and on the App Store.
In version 2.6.0.7 of Domat Visual for Android, saving the default template after launching the application does not work – the app always starts with the DEMO template. Please update to the latest version 2.7.0.1.
The installation package includes the Domat Visual application for industrial iPCs with the Windows operating system for user interface visualization. The application is fully compatible with PLCs using Domat RT and SoftPLC RT.
If you use the Domat Visual application on a standard PC, it will start in full-screen mode (without mouse cursor) after clicking the icon. If this behavior does not suit you, you can modify the desktop shortcut (change the target to “C:\Apps\Domat Visual\DomatVisual.exe”) or run the application directly by double-clicking on c:\Apps\Domat Visual\DomatVisual.exe.