Rcware does not work with bulk DB reading

If the bulk DB reading does not work in rcware and when reading the DB individually, the DBs are read, but then the communication stops somewhere.

Probably, during the creation of the project in the rcware "data editor" there was a transition between the IDE and RT versions on the relevant PLC. The solution is to delete the DBs linked to the time programs and create them again.