Communication works for SoftPLC (not MiniPLC) and Vision with driver via M080, 2400, 7, Even, 1, without flow control.
Attention - in tech. ZPA specification No. C-7.2.22-August 2001 is the reverse polarity of RS485 on the RJ45 connector ("FCC Plug").
1 - power supply
2 - power supply
3 - power supply
4 - RS485 -
5 - RS485 +
6 - power supply 2
7 - power supply 2
8 - power supply 2
The power supply can be 12… 24 V DC (any polarity) or 24 V AC. In order for this to communicate, the 12..24 V power supply must be connected even when the meter is under 230 V voltage!
To make sure that our site works in the best way possible and provides you with the best user experience, we recommend allowing all types of cookies. Below you have the opportunity to edit cookies by category, in line with your own preferences. By pressing the "OK" button, you agree to the setting of cookies so that we can provide you with meaningful and useful services based on your data. You can change your consent at any time on the Personal Data Processing Page.