If the IPLC does not communicate via the Ethernet port (the LEDs on the port do not light up) and the controller performs a control task and communicates with other I/O modules, the low supply voltage may be the cause of the non-functional Ethernet communication. As soon as this voltage falls below the value stated in the datasheet (eg in our measurments it fluctuated between 8-10 V), IPLC runs the project, but the Ethernet port is turned off. For IPLC, the catalog supply voltage is at least 12 V dc. For modules that switch relays, this can be more - see the catalog sheet for the relevant I/O module.
To make sure that our site works in the best way possible and provides you with the best user experience, we recommend allowing all types of cookies. Below you have the opportunity to edit cookies by category, in line with your own preferences. By pressing the "OK" button, you agree to the setting of cookies so that we can provide you with meaningful and useful services based on your data. You can change your consent at any time on the Personal Data Processing Page.