When using the converter (terminal server) M031 with other than no parity (ie with even or odd), 8 bits of data are transmitted plus one of these parities - a total of 9. Therefore, it is necessary to set switch 4 to the ON position, ie 9 bits. Otherwise it will not work.
We have encountered this, for example, with EMU meters during M-Bus transmission (even parity) via Ethernet using WZC-P60 via RS485 interface, ie M-Bus assembly - WZC-P60 - (RS485) - M031 - (Ethernet) - PC.
The same applies to other converters with parameter setting using pianos (eg M011).
To make sure that our site works in the best way possible and provides you with the best user experience, we recommend allowing all types of cookies. Below you have the opportunity to edit cookies by category, in line with your own preferences. By pressing the "OK" button, you agree to the setting of cookies so that we can provide you with meaningful and useful services based on your data. You can change your consent at any time on the Personal Data Processing Page.