When integrating pulse converters on M-Bus AEW21.1 into MiniPLC (this is an older type, today AEW 310.2 is produced) pay attention to setting timeouts in data point communication parameters (Special params - Telegram timeout): in case of non-communication it is necessary to increase this value from default 400 to 2000 ms.
Please note, for configuration and recording of initial values, a special cable is needed, probably RS232-TTL (?) (for new types AEW310.2 the cable is USB-something, communication via M-Bus is the same). So after M-Bus, the entry of values may not be accessible at all for security reasons.
To make sure that our site works in the best way possible and provides you with the best user experience, we recommend allowing all types of cookies. Below you have the opportunity to edit cookies by category, in line with your own preferences. By pressing the "OK" button, you agree to the setting of cookies so that we can provide you with meaningful and useful services based on your data. You can change your consent at any time on the Personal Data Processing Page.